CONTACT RELAY MODULE PLC 24UC/21

Stock Code:
CRM24V-PLC
Regular Price: $50.02 (inc GST)
Regular Price:
$50.02 (inc GST)
Price:
$45.85 (inc GST)
Quantity Breaks
1+
$45.85 (inc GST)

Description

Relay Module - PLC-RSC- 24UC/21

PLC-INTERFACE, consisting of basic terminal block PLC-BSC.../21 with screw connection and plug-in miniature relay with power contact, for assembly on DIN rail NS 35/7,5, 1 changeover contact, input voltage 24 V AC/DC

Dimensions

Width

6.2 mm

Height

80 mm

Depth

94 mm

 

Ambient conditions

Ambient temperature (operation)

-40 °C ... 60 °C

Ambient temperature (storage/transport)

-40 °C ... 85 °C

 

Coil side

Nominal input voltage UN

24 V AC/DC

Input voltage range in reference to UN

see diagram

Typical input current at UN

11 mA (at UN = 24 V AC)
8.5 mA (at UN = 24 V DC)

Typical response time

6 ms

Typical release time

15 ms

Coil voltage

24 V DC

Protective circuit

Bridge rectifier

Operating voltage display

Yellow LED

Power dissipation for nominal condition

0.26 W

Contact side

Contact type

1 changeover contacts

Type of switch contact

Single contact

Contact material

AgSnO

Maximum switching voltage

250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)

Minimum switching voltage

5 V (at 100 mA)

Min. switching current

10 mA (At 12 V)

Maximum inrush current

12 A (20 ms, N/O contacts)

Limiting continuous current

6 A (see diagram)

Interrupting rating (ohmic load) max.

 

 

 

 

 

140 W (at 24 V DC)

20 W (at 48 V DC)

18 W (at 60 V DC)

23 W (at 110 V DC)

40 W (at 220 V DC)

1500 VA (for 250 V AC)

Switching capacity

 

2 A (at 24 V, DC13)

0.2 A (at 230 V, AC15)

0.1 A (at 220 V, DC13)

3 A (at 24 V, AC15)

3 A (at 120 V, AC15)

3 A (at 230 V, AC15)

Connection data input side

Connection method

Screw connection

Stripping length

8 mm

Conductor cross section solid

0.14 mm² ... 2.5 mm²

Conductor cross section flexible

 

 

0.14 mm² ... 2.5 mm²

0.2 mm² ... 2.5 mm² (Single ferrule)

2 x 0.5 mm² ... 1.5 mm² (TWIN ferrule)

Conductor cross section AWG

 

26 ... 16

Connection data output side

Connection method

Push-in connection

Stripping length

8 mm

Conductor cross section solid

0.14 mm² ... 1.5 mm²

Conductor cross section flexible

 

 

0.14 mm² ... 1.5 mm²

0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)

0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)

Conductor cross section AWG

 

26 ... 16 (solid)

26 ... 16 (flexible)

 

General

Test voltage relay winding/relay contact

4 kVrms (50 Hz, 1 min.)

Operating mode

100% operating factor

Degree of protection

 

IP20 (Relay base)

Mechanical service life

approx. 2 x 107 cycles

Mounting position

Any

Assembly instructions

In rows with zero spacing

 

Standards and Regulations

Standards/regulations

IEC 60664, EN50178

Insulation

Safe isolation, basic insulation, and 4 kV rated surge voltage between all changeover contacts.

Degree of pollution

3

Overvoltage category

III

Flammability rating according to UL 94

V0 (Housing)